Dualcom PLUS gives you power to do it better.
The Dualcom PLUS not only allows remote power management, but also represents a new approach to managing your system. Save energy by scheduling shutdown periods. Monitor current consumption to utiliize valuable rack space efficiently. Your network is your responsibility...

Dualcom PLUS means power control and monitoring from wherever you are.


The Dualcom PLUS enables scheduled or manual on/off control of eight individual outlets, and monitoring of the current supplied by each outlet. Three interfaces provide convenient access to your system:


TCP/IP: Web, Telnet, SNMP
The Ethernet interface can be utilized either through a text based telnet session or through an http web interface. The telnet session works identical to the serial interface in that it's text based and the menus are identical. The web interface utilizes a web browser and the Hypertext Transfer Protocol (HTTP). This interface looks and feels different from the others in that it's a GUI (graphical user interface).

Serial Port
The Serial interface uses a standard serial port protocol, so that any laptop or pc with an available com port can utilize this direct connection to the unit. The serial port is also utilized as the initial setup port for the unit. The other interface's need to be setup before they can be used. Once that has been done, all the settings can now be managed through the serial or Ethernet ports.


Features

  • Events tracked in an event log, including change of outlet states, logins and logoffs, and IP address of logins
  • Receive event logs via e-mail automatically
  • Assign descriptive names to each outlet
  • Outlet states and total system current displayed on front panel
  • Outlet memory restores outlet states in event of power outage
  • Overcurrent warning provided on front panel
  • Adjustable stagger start of outlets helps protect plugged in hardware when power is restored

Specifications

Output
  • Output Voltage 208-240 VAC
  • Output Connections (16) IEC 60320 C13
  • Output Current per Bank 20 A
  • Output Current per Receptacle 15 A
Input
  • Input Voltage 208-240 VAC
  • Input Frequency 50/60 Hz
  • Input Connection Type* NEMA L6-30P
  • Cord Length 12 feet
  • Circuit Breaker (2) 20A UL Listed
  • Input Current 30A
  • Load Capacity 7200 VA

*other input cord plug options available

Physical
  • Net Weight 10.10 lbs.
  • Maximum Height 65.00 inches
  • Maximum Width 1.75 inches
  • Maximum Depth 2.75 inches
  • Shipping Weight 13.10 lbs.
  • Shipping Height 72.00 inches
  • Shipping Width 7.50 inches
  • Shipping Depth 4.50 inches
  • Color Black
Environmental
  • Operating Environment 0 to 45 °C
  • Maximum Operating Relative Humidity 95%
  • Storage -25 to 85 °C
  • Regulatory Approval (Pending) cUL Listed, UL Listed, IEC 60950-1, FCC Class A
Communication
  • Network Settings 10BaseT
  • Serial Settings RS-232 (Cisco DCE pin-out)

DERATE TO 80% FOR CONTINUOUS LOAD